User Manual

Application Sheet FCU032
Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac
output and electric reheater
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_d_--_02
Heating with LTHW and cooling with CHW changeover
Modulating control of heating and cooling valve (2 pipe) on triac output and electric reheater
Automatic or manual variable fan speed control DC 0...10 V
Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
Plant diagram
DXR2… Room automation station Q1 Variable speed fan
B1 Extract air temperature sensor R Room
B3 Supply air temperature sensor R1 Room operator unit with
D1 Window contact temperature sensor
D2 Presence detector YHC Heating/cooling coil valve
D4 Over-temperature detector YR Electric reheater
Function diagrams Heating/cooling valves DC 0...10 V fan
Electric reheater, 1-stage
Chovr Changeover SpH Effective heating setpoint
C Cooling sequence TR Room temperature
H Heating sequence Y Output signal
Q Fan output signal YHC Heating/cooling valve
SpC Effective cooling setpoint YR Electric reheater
SpC
0
100
Y [%] Q [%]
TR [°C]
YH
SpH
YC
100
Chovr
SpC
TR [°C]
YHC YHC
0
SpH
Y [%]
H C