Data Sheet for Application
Application Sheet
CBP002/CBP002_H
Passive chilled/heating beam (2 pipe) with changeover on triac
output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-26
A6V10662233_en--_c_--_09
• Heating or cooling with passive chilled/heating beam with changeover on triac outputs
• Modulating control of heating and cooling valve
• Condensation monitoring
• Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
DXR2…
Room automation station
R
Room
D1
Window contact
R1
Room operator unit with
D2
Presence detector
temperature sensor
D3.1
Condensation monitor 1
YHC1
Heating/cooling valve 1
D3.2
Condensation monitor 2
YHC2
Heating/cooling valve 2
Function diagrams
Heating/cooling valves
Chovr
Changeover
SpH
Effective heating setpoint
C
Cooling sequence
TR
Room temperature
H
Heating sequence
Y
Output signal
SpC
Effective cooling setpoint
YHC
Heating/cooling valve
100
Chovr
SpC TR [°C]
YHC YHC
0
SpH
Y [%]
H C