Data Sheet for Application

Application Sheet
CBP002/CBP002_H
Passive chilled/heating beam (2 pipe) with changeover on triac
output
DXR2..09T-101A
5 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-26
A6V10662233_en--_c_--_09
Optional
configuration
Equipment
Values/Range
Template settings
On-board output
Chilled/heating beam valve position 2
Chilled; Y1, Y2; 3-position
Chilled; Y3, Y4; 3-position
Chilled; Y2; Pulse width modulation thermal
Chilled; Y3; Pulse width modulation thermal
Heating/chilled 2-pipe; Y1, Y2; 3-position
Heating/chilled 2-pipe; Y3, Y4; 3-position
Heating/chilled 2-pipe; Y2; Pulse width
modulation thermal
Heating/chilled 2-pipe; Y3; Pulse width
modulation thermal
Heating; Y1, Y2; 3-position
Heating; Y3, Y4; 3-position
Heating; Y2; Pulse width modulation thermal
Heating; Y3; Pulse width modulation thermal
Chilled beam passive; Y1, Y2; 3-position
Chilled beam passive; Y3, Y4; 3-position
Chilled beam passive; Y2; Pulse width
modulation thermal
Chilled beam passive; Y3; Pulse width
modulation thermal
Heat/chilled beam passive 2-pipe; Y1, Y2; 3-
position
Heat/chilled beam passive 2-pipe; Y3, Y4; 3-
position
Heat/chilled beam passive 2-pipe; Y2; PWM
thermal
Heat/chilled beam passive 2-pipe; Y3; PWM
thermal
Heat/chilled beam passive
2-pipe; Y3, Y4; 3-position
On-board input
Presence detector 2 (D2
a
)
X1, Normally open
Window contact (D1)
D1; Normally closed
Condensation monitor (D3.1, D3.2)
X2; Normally closed
KNX PL-Link devices
Sensor device 1…4 (D2)
UP 258D12
Default values
Parameter
Values/Range
Template settings
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Heating setpoint for Comfort
0 … 50 °C
21 °C
Delta heating setpoint for Pre-comfort
0 … 10 K
1 K
Heating setpoint for Economy
0 … 50 °C
15 °C
Heating setpoint for Protection
0 … 50 °C
12 °C
Chilled/heating beam
Enable condensation monitor input
Yes, No
Yes