User Manual

Application Sheet CBA002
Active chilled beam with variable fan, cooling coil and hot water
radiator on triac output
DXR2..09T-101A
2 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_b_--_10
Description
of functions
Basic functions Options
PID control for cooling.
3-position valves are controlled by triac outputs for
cooling.
The fan is controlled manual on the room operator unit
or automatic with variable speed.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
Optional radiator.
PID control for LTHW radiator heating.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
fan coil unit application.
Standard hot and cold water supply chain control.
The application allows for control via centralized
commands (e.g. scheduler program
for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices Legend Type of unit Data sheet Product No. Qty.
DXR2… Compact room automation station, BACnet/IP, 230 V,
flat housing, 1 DI, 2 UI, 1 DO relay, 4 DO triacs,
1 AO 0…10 V
N9204
N9206
DXR2.E09T-101A
DXR2.M09T-101A
1
R1 KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602 QMX3.P34 1
YC 2-port, 3-port valve or 3-port valves with bypass, PN16 N4847 V..P47.. 1
Motorized 3-positioning actuator for V..P47.., AC 24 V N4864 SSP81.. 1
Optional
1)
Legend Type of unit Data sheet Product No. Qty.
B1 Cable temperature sensor PVC 2 m, LG-Ni1000 N1831 QAP22 1
B3 Cable temperature sensor PVC 2 m, LG-Ni1000 N1831 QAP22 1
D1 Door/window contact, white
2)
S 290/11
3)
D2 KNX PL-Link presence detector
2)
UP 258D12 1 - 4
YR 2-port, 3-port valve or 3-port valves with bypass, PN16 N4847 V..P47.. 1
Motorized 3-positioning actuator for V..P47.., AC 24 V N4864 SSP81.. 1
1)
Can be combined according to available on-board I/Os on controller.
2)
Further documents on www.siemens.com/gamma-td.
3)
Type of operation (NO or NC). Multiple devices of the same type can be connected.