Data Sheet for Application

Application Sheet
CCG011/CCG011_H
Chilled ceiling on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-27
A6V10662233_en--_e_--_04
Cooling with chilled ceiling on triac outputs
Modulating control of cooling valve
Condensation monitoring
Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
Room automation station
R
Room
Window contact
R1
Room operator unit with
Presence detector
temperature sensor
Condensation monitor 1
YC1
Cooling valve 1
Condensation monitor 2
YC2
Cooling valve 2
Function diagrams
Cooling valve
Cooling sequence
Y
Output signal
Effective cooling setpoint
YC
Cooling valve
Room temperature
SpC
0
100
Y [%]
TR [°C]
YC
C