Data Sheet for Application

Application Sheet
CCG011/CCG011_H
Chilled ceiling on triac output
DXR2..09T-101A
2 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-27
A6V10662233_en--_e_--_04
Description
of functions
Basic functions
Options
PID control for cooling.
3-position valves are controlled by triac outputs for
cooling.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
2
nd
chilled ceiling.
Condensation monitoring.
Optimal energy efficiency by presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP, 230 V,
flat housing, 1 DI, 2 UI, 1 DO relay, 4 DO triacs,
1 AO 0…10 V
N9204
N9206
DXR2.E09T-101A
DXR2.M09T-101A
1
R1
KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602
QMX3.P34
1
YC1
2-port, 3-port valve or 3-port valves with bypass, PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC 24 V
N4864
SSP81..
1
Optional
1)
Legend
Type of unit
Data sheet
Product No.
Qty.
D1
Door/window contact, white
2)
S 290/11
3)
D2
KNX PL-Link presence detector with brightness sensor
2)
UP 258D12
1 - 4
D3.1
Condensation monitor
A6V10741072
QXA21..
1
D3.2
Condensation monitor
A6V10741072
QXA21..
1
YC2
2-port, 3-port valve or 3-port valves with bypass, PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC 24 V
N4864
SSP81..
1
1)
Can be combined according to available on-board I/Os on controller.
2)
Further documents on www.siemens.com/gamma-td.
3)
Type of operation (NO or NC). Multiple devices of the same type can be connected.