Data Sheet for Application

Application Sheet
CCG011/CCG011_H
Chilled ceiling on triac output
DXR2..09T-101A
5 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-27
A6V10662233_en--_e_--_04
Default values
Parameter
Values/Range
Template settings
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Radiant ceiling
Enable condensation monitor input
Yes, No
Yes
Room operator unit
Room unit, display temperature
None
Display room temperature
Display room temperature
Room unit, display windows status
Yes, No
No
Room unit, display heat./cool. status
Yes, No
Yes
Enable operation: room temp.
setpoint
Yes, No
Yes
Room unit, room temp. setpoint
display
Absolute temperature setpoint
Relative setpoint shift
Relative setpoint shift
Enable operation: fan speed setpoint
Yes, No
No
Enable operation: presence button
Yes, No
No
Enable operation: temporary Comfort
Yes, No
No
Enable operation: room op. mode
Yes, No
No
Enable operation: Green Leaf
Yes, No
Yes
Engineering
ABT Site engineering tool is required to configure the DXR2 automation stations.
See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
Option combination according to available on-board I/Os on controller.
D2
a
(on-board presence detector) to be configured in ABT Site under ‚Presence detector 2‘ for maximum
combination of optional devices.
Type of operation (N/O or N/C). Multiple devices of the same type can be connected.
Management
station
Sample presentation of a chilled ceiling application on the Desigo CC management station.