Data Sheet for Application

Application Sheet
INT061
Chilled ceiling with hot water radiator on triac output including
lighting and blinds operation
DXR2..09T-101A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662233_en--_e_--_07
Heating with radiator/floor heating and cooling with chilled ceiling on triac outputs
Modulating control of heating and cooling valve on triac outputs
Downdraft compensation
Condensation monitoring
Including the control of 4 lighting zones & 2 blinds
Room temperature operation via KNX PL-Link room operator unit with temperature measurement &
lighting and blinds operation
Plant diagram
Room automation station
Q6, Q7
2 blinds motors
Window contact
R
Room
Presence detector
R1
Room operator unit with
Condensation monitor
temperature sensor
4 lighting zones
YC
Cooling valve
YR
Radiator valve
Function diagrams
Heating/cooling valves
Cooling sequence
TR
Room temperature
Heating sequence
Y
Output signal
Effective cooling setpoint
YC
Cooling valve
Effective heating setpoint
YH
Heating valve
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
C
H