User Manual

Application Sheet CBP001
Passive chilled beam (2 pipe) with hot water radiator on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_b_--_08
Heating with radiator/floor heating and cooling with passive chilled beam (2 pipe) on triac outputs
Modulating control of heating and cooling valve
Downdraft compensation
Condensation monitoring
Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
DXR2… Room automation station R1 Room operator unit with
D1 Window contact temperature sensor
D2 Presence detector YC Cooling valve
D3 Condensation monitor YR Radiator valve
R Room
Function diagrams
Heating/cooling valves
C Cooling sequence TR Room temperature
H Heating sequence Y Output signal
SpC Effective cooling setpoint YC Cooling valve
SpH Effective heating setpoint YH Heating valve