Data Sheet for Application

Application Sheet
CCG021/CCG021_H
Chilled ceiling with hot water radiator on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-27
A6V10662233_en--_e_--_05
Heating with radiator/floor heating and cooling with chilled ceiling on triac outputs
Modulating control of heating and cooling valve
Downdraft compensation
Condensation monitoring
Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
Room automation station
R1
Room operator unit with
Window contact
temperature sensor
Presence detector
YC
Cooling valve
Condensation monitor
YR
Radiator valve
Room
Function diagrams
Heating/cooling valves
Cooling sequence
TR
Room temperature
Heating sequence
Y
Output signal
Effective cooling setpoint
YC
Cooling valve
Effective heating setpoint
YH
Heating valve
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
C
H