User Manual

Application Sheet CBP002
Passive chilled/heating beam (2 pipe) with changeover on triac
output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_b_--_09
Heating or cooling with passive chilled/heating beam with changeover on triac outputs
Modulating control of heating and cooling valve
Condensation monitoring
Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
DXR2… Room automation station R Room
D1 Window contact R1 Room operator unit with
D2 Presence detector temperature sensor
D3.1 Condensation monitor 1 YHC1 Heating/cooling valve 1
D3.2 Condensation monitor 2 YHC2 Heating/cooling valve 2
Function diagrams
Heating/cooling valves
Chovr Changeover SpH Effective heating setpoint
C Cooling sequence TR Room temperature
H Heating sequence Y Output signal
SpC Effective cooling setpoint YHC Heating/cooling valve
100
Chovr
SpC
TR [°C]
YHC YHC
0
SpH
Y [%]
H C

Summary of content (6 pages)