Data Sheet for Application

Application Sheet
FCU032/FCU032_H
Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac
output and electric reheater
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662233_en--_e_--_02
Heating with LTHW and cooling with CHW changeover
Modulating control of heating and cooling valve (2 pipe) on triac output and electric reheater
Automatic or manual variable fan speed control DC 0...10 V
Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
Plant diagram
Room automation station
Q1
Variable speed fan
Extract air temperature sensor
R
Room
Supply air temperature sensor
R1
Room operator unit with
Window contact
temperature sensor
Presence detector
YHC
Heating/cooling coil valve
Over-temperature detector
YR
Electric reheater
Function diagrams
Heating/cooling valves
DC 0...10 V fan
Electric reheater, 1-stage
Chovr
Changeover
SpH
Effective heating setpoint
C
Cooling sequence
TR
Room temperature
H
Heating sequence
Y
Output signal
Q
Fan output signal
YHC
Heating/cooling valve
SpC
Effective cooling setpoint
YR
Electric reheater
SpC
0
100
Y [%] Q [%]
TR [°C]
YH
SpH
YC
100
Chovr
SpC TR [°C]
YHC YHC
0
SpH
Y [%]
H C
0
100
Y [%]
TR [°C]
YH
SpH
YR

Summary of content (6 pages)