Data Sheet for Application
Application Sheet
FCU042/FCU042_H
Fan coil unit with variable fan speed, heating and cooling coil
(4 pipe) on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662233_en--_e_--_01
• Heating with LTHW and cooling with CHW
• Modulating control of heating and cooling valve (4 pipe) on triac output
• Automatic or manual variable fan speed control DC 0...10 V
• Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
Plant diagram
DXR2…
Room automation station
R
Room
B1
Extract air temperature sensor
R1
Room operator unit with
B3
Supply air temperature sensor
temperature sensor
D1
Window contact
YC
Cooling coil valve
D2
Presence detector
YH
Heating coil valve
Q1
Variable speed fan
Function diagrams
Heating/cooling valves
DC 0...10 V fan
Q
Fan output signal
Y
Valve output signal
SpC
Effective cooling setpoint
YC
Cooling coil valve
SpH
Effective heating setpoint
YH
Heating coil valve
TR
Room temperature
SpC
0
100
Y [%] Q [%]
TR [°C]
YH
SpH
YC
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC