Data Sheet for Application

Application Sheet
RAD011/RAD011_H
Hot water radiator on triac output
DXR2..09T-101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662233_en--_d_--_03
Heating with LTHW radiator
Modulating control of heating valve on triac output
Downdraft compensation
Room temperature operation via KNX PL-Link room operator unit with temperature measurement
Plant diagram
Room automation station
R1
Room operator unit with
Window contact
temperature sensor
Presence detector
YR1
Radiator valve 1
Room
YR2
Radiator valve 2
Function diagrams
Heating valve
H
Heating sequence
Y
Output signal
SpH
Effective heating setpoint
YH
Heating valve
TR
Room temperature
0
100
Y [%]
TR [°C]
YH
SpH
H