Assortment / System Description

VAV application
Air volume flow in the dead zone
18
122 | 275 A6V10866237_en--_b_08
The control strategy can be configured in the application using the following
parameters for heating sequence.
Description Name Default value
Operating variables volume flow system for cooling
0:Serial
1:Parallel
VavOp 1:Parallel
Operating variables volume flow system for heating
0:Serial
1:Parallel
VavOp 1:Parallel
18.2 Air volume flow in the dead zone
The VAV application configures a minimum supply air flow in the temperature
control dead zone. The function can be configured individually for all room
operating mode.
Description Name Default value
Minimum supply air Comfort
1:Off
2:Minimum ventilation
3:Demand-controlled ventilation
4:Minimum & demand-controlled ventilation
CmfCnf 4:Minimum
ventilation &
demand-
controlled
ventilation
Minimum supply air for Pre-Comfort. PcfCnf 3:Demand-
controlled
ventilation
Minimum supply air Economy EcoCnf 1:Off
Minimum supply air Protection PrtCnf 1:Off
Minimum air volume flow for all room operating modes is also configured.
Description Name Default value
Supply air VAV minimum air flow for ventilation VavSuAflMinVnt 0 [m3/h]
0.00 [l/s]