Assortment / System Description

Room pressurization and fume hood control
Pressurized room, temperature control
21
A6V10866237_en--_b_08 203 | 275
Description Object Default value
Supply air VAV balancing state
Indicates the state of progress of the
balancing process for this VAV box. It is
written by the controller in response to the
user-entered balance command. It persists
through a power cycle.
1:Initial
2:Balancing
3:Balanced
VavSuBalSta 1:Initial
Supply air VAV balancing mode
Air flow value set by the air balancer person
to select the air flow setpoint value used when
the balancing state = balancing.
1:Maximum cooling
2:Maximum heating
3:Maximum ventilation
4:Minimum cooling
5:Minimum heating
6:Minimum ventilation
7:Smoke
VavSuBalMod 1:Maximum cooling
Supply air VAV duct area
Duct cross-sectional area, user-entered or
calculated by controller using the duct shape,
dimension A and dimension B values.
0…1 [m
2
], 0.0…10.76 [ft
2
]
VavSuDuctArea 0.05 [m
2
]
0.54 [ft
2
]
Supply air VAV flow coefficient
The value used to calibrate span of air flow
measurement. The value of calc flow
coefficient is written to this object upon the
Calibrate command.
VavSuFlCoef 0.780
Supply calibration