Assortment / System Description

Central applications
Automation station for HVAC supply and demand signals and manual control for lighting and blinds
24
242 | 275 A6V10866237_en--_b_08
Each of the central commands for the room operating mode can be delayed in
the building using three additional groups. It is used primarily in buildings with
larger facades if control influences act on facades for a change to the room
operating mode. The delay can be configured.
Description Name Default value
Central operating mode delay 1
0...7200 [s]
CenOpModDly1 10 [s]
Central operating mode delay 2
0...7200 [s]
CenOpModDly2 20 [s]
Central operating mode delay 3
0...7200 [s]
CenOpModDly3 30 [s]
24.1.2 Manual control of lighting & blinds via KNX PL-Link
The following input signals can be read to DXR2 for the central, manual control
for lighting and blinds:
Command Inputs Information is used for
Manual operation lighting 1 KNX PL-Link Application: Central manual
operation lighting
Manual operation lighting 2 KNX PL-Link Application: Central manual
operation lighting
Manual operation shading
products 1
KNX PL-Link Application: Central operation
of shading products
Manual operation shading
products 2
KNX PL-Link Application: Central operation
of shading products
Delay function on large
facades