Assortment / System Description

Central applications
Automation station for hierarchical grouping of central applications
24
268 | 275 A6V10866237_en--_b_08
NOTICE
It must also be disabled through configuration if HVAC emergency shut
down is not used.
Description Name Default value
Enable fire detector:
0:No
1:Yes
EnFireDet 1:Yes
24.5.3 Automation station for weather station, floor level
(Cen-Flr)
The DXR2 for central weather station, floor level (Cen-Flr) can process
measured values for outside temperature, precipitation, wind, and relative air
humidity and provides the weather information to the widest range of
applications or room operator units.
The function is part of application types for central functions and can be loaded
to a DXR2.E/M18.
The following weather information can also be read on the DXR2 for the central
weather station, floor level (Cen-Flr):
Sensor Inputs Information is used for
Outside air temperature None:
Superposed measurement on
the automation station on the
building level (Cen-Bldg) wins
- - -
Precipitation Binary input (NO contact):
Local measurement on the
automation station, floor level
(Cen-Flr) wins against the
superposed measurement,
building level (Cen-Bldg)
Application: Precipitation
protection for awnings
Wind 0…10V:
Local measurement on the
automation station, floor level
(Cen-Flr) wins against the
superposed measurement,
building level (Cen-Bldg)
Application: Wind protection for
facade products
Relative humidity None:
Superposed measurement on
the automation station on the
building level (Cen-Bldg) wins
- - -