Assortment / System Description

Room coordination functions
Room functions: Room coordination
13
62 | 275 A6V10866237_en--_b_08
For lighting applications, lighting can be switched on, off, or reset to automatic
using the triggers "Energy efficiency condition" and "Comfort condition".
The application can also recognize whether the change to the room operating
mode from an automatic function or was the result of a manual operation. It
can also be considered during configuration.
Description Name Default value
Operating command for the energy efficiency
condition trigger on automatic
1:None
2:Automatic
3:Lighting on
4:Lighting off
5:Lighting off/warning (reset)
5:Lighting off/warning (permanent)
OpCmdEefAuto 1:None
Operating command for the energy efficiency
condition trigger on manual
OpCmdEefMan 1:None
Operating command for the Comfort condition trigger
on automatic
OpCmdCmfAuto 1:None
Operating command for the Comfort efficiency
condition trigger on manual
OpCmdCmfMan 1:None
For blinds applications, blinds can be held or reset to automatic using the
triggers "Energy efficiency condition" and "Comfort condition".
The application can also recognize whether the change to the room operating
mode from an automatic function or was the result of a manual operation. It
can also be considered during configuration.
Description Name Default value
Operating command for the energy efficiency
condition trigger on automatic
1:None. No reaction to trigger.
2:Automatic. Blinds are automatically reset to
automatic. It is used to deactivate any manual
operation of blinds, if the room is no longer occupied.
3:Hold. The blinds remains in the actual position and
are reset to manual. This prevents unintended
movement of blinds by the automatic functions when
the room is occupied.
OpCmdEefAuto 2:Automatic
Operating command for the energy efficiency
condition trigger on manual
OpCmdEefMan 2:Automatic
Operating command for the Comfort condition trigger
on automatic
OpCmdCmfAuto 1:None
Operating command for the Comfort efficiency
condition trigger on manual
OpCmdCmfMan 1:None
Impact of the trigger on
Light
Impact of the trigger on
blinds