5 Installation box / panel for TRA
5.1 Requirements
Please read Sections 5.1 "Panel requirements" and 5.3 "EMC compliant panel" in
the TX-I/O engineering and installation guide [8] prior to engineering and executing
the installation box.
Observer the following for mounting and installation.
Installation depth
Maintain sufficient cable distance to be able to easily snap on and remove the
screw terminal blocks, even if the automation stations are mounted.
Room automation stations can be mounted directly next to one another; a
distance of ca. 2 cm is recommended, however, for facilitate access.
Reserve sufficient free space for subsequent extensions.
The room automation stations and TX-I/O modules are designed for installation on
standard rails (prerequisite to establishing the island bus connection using TX-I/O
modules).
Permissible standard rails:
· Top hat rails TH35-7.5 as per EN60715 (35 x 7.5 mm).
· Other top hat rails that meet the following conditions:
Material thickness exterior max. 1 mm, min. 3 mm in depth
Internal opening at least 25 mm.
min. 25
35
35
10762M044
(25)
35 ± 0,3
27 ± 0,2
1 ± 0.04
7.5
-0.4
0
1 ± 0.04
min. 3
min. 6.5
min. 25
min. 6.5
The room automation station may also be attached to a wall if used without TX-I/O
modules.
Systems with TX-I/O
modu
l
es
Space requirements
Installation mode
Standard rails
Wall mounting