Data Sheet for Application
Table Of Contents
Application Sheet VAV042/VAV042_H
Supply and extract VAV with integrated damper actuator, heating
and cooling coil on triac output
DXR2..10PL..
1/ 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V11463709_en--_b
Supply & extract air volume control with integrated damper actuator (10 Nm)
Room temperature control
Air quality control
Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature, air quality & relative humidity measurement
Plant diagram
DXR2… Room automation station R Room
B1 Extract air temperature sensor R1 Room operator unit with
B3 Supply air temperature sensor temperature sensor
B4 Differential pressure sensor
(supply air – integrated of DXR2)
YC Cooling coil valve
B5 Differential pressure sensor
(extract air)
YE Extract air control
D1 Window contact YH Heating coil valve
D2 Presence detector YS Supply air control (integrated of DXR2)
Function diagrams Heating and cooling valve Air flow
SpC Effective cooling setpoint
VavSuAirFlMaxH
Max. volume, heating
SpH Effective heating setpoint
VavSuAirFlMinC
Min. volume, cooling
TR Room temperature
VavSuAirFlMinH
Min. volume, heating
V Volume flow rate Y Output signal
VavSuAflMinVent
Min. air flow ventilation YC Cooling valve
VavSuAirFlMaxC
Max. volume, cooling YH Heating valve