Desigo™ Room Automation Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR) DXR2.E10PL-102B, DXR2.E10PLX-102B Combination room automation station and actuator for buildings with increased demands placed on functionality and flexibility in Room Automation applications, VAV, Dual Duct and FPB applications.
Features Programmable The DXR2... automation stations provide the infrastructure for system and application-specific functions and can be programmed. Compact series The compact build permits mounting directly on the damper shaft, and is designed for VAV and FPB. Plug-in terminal blocks Plug-in terminal blocks to easily exchange room automation stations. Integrated actuator The actuator gear base is integrated into the housing of the actuating DXR. For dampers requiring up to 88 lb-in (10 Nm) of torque.
Communication ● 2-Port Ethernet switch for cost-effective cabling via line topology. ● USB connection for service and commissioning, firmware download, and LAN access. ● The following functions are available with the KNX PL-Link bus: – Communication with room operator units, switches, sensors, actuators, and luminaires. – Plug-and-play connection of Siemens field devices with KNX PL-Link. – Integration of common devices using KNX S-Mode (ETS engineering required).
Type summary Type Order number Inputs Outputs DXR2.E10PL-102B (Version with 30 data points) S55376-C145 1 DI, 2 UI, 1 ΔP sensor 4 DOs, 1 AO. DXR2.E10PLX-102B (Version with 60 data points) S55376-C146 1 DI, 2 UI, 1 ΔP sensor 4 DOs, 1 AO. Product documentation Topic Title Document ID: Installation, cable length, topology Desigo Room Automation installation guide CM111043 Engineering and commissioning, workflow ABT online help n.a.
Triac outputs AC 24 V Individual Triac outputs may have a max. load of 12VA. The following possibilities are permitted: ● Internal floating control actuator. ● One or two motorized actuators with 6 VA each. ● 1 to 4 binary outputs with 12 VA load each. ● 1 or two thermal actuator(s) with 6 VA start load each in a cold state. For transformer design (voltage drop), each thermal actuator must be counted at the full start load, since the Triac outputs can be freely controlled.
Operation The outputs have no electricity when power fails. USB communications failure can be caused by weak or incorrect grounding at DXR 24 V power termination. (The power terminal labeled ⏊ must be connected to earth ground.) Disposal The device is considered an electronics device for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose.
Power data Power supply Operating voltage AC 24 V -15%/+20% Frequency 50/60 Hz Internal fuse 4 A irreversible Transformer with secondary current limitation of max. 10 A or external secondary current fuse Non-renewable fuse Circuit breakers Max. 10 A, (Class 2, 4A) Max. 13 A, characteristic B, C, D as per EN 60898 Apparent power (VA) for transformer design Base load including I/O without load by field devices Max. output load Triac at 500 mA each Max. load for AC 24 V field supply at 200 mA Max.
Voltage measurement, analog (inputs X...) Type Range (over range) Resolution AI 0...10 V 0...10 V (-1...11 V) 2 mV AI 0...10 V standard 0...100% (-10...110%) 2 mV Open connection: Negative voltage -1.5 V, 8 μA (line failure detection) Digital input (inputs X... or D...) Contact query voltage Universal input: 18 V Digital input: 21 V Contact query current Universal input: 1.2 mA, 7.4 mA initial current Digital input: 1.6 mA; 9.4 mA initial current Contact resistance for closed contacts Max.
Connections Interfaces Ethernet Plugs: 2 x RJ45, screened Interface type: 10Base-T/100BASE-TX, IEEE 802.3 compatible Bitrates: 10/100 Mbps, autosensing Protocol: BACnet over UDP/IP USB (2.0) Plug: Type B Data rate: 12 Mbps KNX Type: KNX TP1 PL-Link, galvanic isolation Baud rate: 9.6 kbps Bus power: 50 mA Short-circuit proof Protection against faulty wiring at max. AC 24 V Wiring connections Pluggable screw terminals Copper wire or copper stranded wire with connector sleeves 1 x 0.6 mm ø to 2.
Conformity Ambient conditions and protection classification Classification per IEC/EN 60730 Function of automatic control devices Pollution degree Overvoltage category Type 1 2 III Device suited for use with equipment of safety classes I and II Design type Degree of protection of housing to IEC EN 60529 Room automation station IP20 IP30 Climatic ambient conditions ● Transport (packaged for transport) as per IEC EN 60721-3-2 ● ● ● Operation as per IEC/EN 60721-3-3 Mechanical ambient conditions Trans
Connection terminals Pin Description 1, 2 Ethernet 2 x RJ45 interface for 2-port Ethernet switch 11, 12 KNX KNX connection USB USB interface 51...52 power 24V~ 64...69 Triac outputs 71 Digital output 73…77 Siemens Smart Infrastructure Terminal Module Channel +, - Power supply SELV / PELV AC 24V V~ System neutral ⏊ Switching output AC 24V Y3…Y6 11 3…6 Positioning output DC 0...
Dimensions Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 12 Siemens Smart Infrastructure Document ID A6V11259958_en--_b Edition 2020-01-16 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.