Assortment / System Description

VAV application
Dynamic calibration
18
A6V10866237_en--_b_08 147 | 275
Description Name Default value
Supply air VAV calibration command
0:Ready
1:Balancing
2:Calibrate
3:Record
4:Balanced
VavSuBalCmd 0:Ready
Supply air VAV balancing state VavSuBalSta 1:Initial
Supply air VAV balancing operating mode
0:Maximum cooling
1:Maximum heating
2:Maximum ventilation
3:Minimum cooling
4:Minimum heating
5:Minimum ventilation
6:Manual
VavSuBalMod 0: Maximum
cooling
Supply air flow hood VavSuAirFlHood 100 [m
3
/h]
Supply air VAV recorded balancing operating mode
0:Maximum cooling
1:Maximum heating
2:Maximum ventilation
3:Minimum cooling
4:Minimum heating
5:Minimum ventilation
6:Manual
VavSuBalModRec 1: Maximum
cooling
Supply air VAV recorded air flow hood VavSuAflHodRec 0 [m
3
/h]
Supply air VAV recorded flow coefficient VavSuFlCoefRec 0
Supply air VAV initial flow coefficient VavSuFlCoefIni 0
Supply air VAV recorded air flow VavSuAirFlRec 0 [m
3
/h]
Variable air flow supply air recorded position VavSuPosRec 0 [%]
Supply air VAV duct surface area VavSuDuctArea 0.05 [m
2
]
Supply air VAV duct shape VavSuDuctShape 2:Round
Supply air VAV dimension A VavSuDmsnA 20 [cm]
Supply air VAV dimension B VavSuDmsnB 20 [cm]
Supply air VAV flow coefficient VavSuFlCoef 0.78
Supply air VAV smoke extraction air volume flow
setpoint
VavSuSpAflSmk 50 [m
3
/h]
Supply air VAV maximum air volume flow for cooling VavSuAirFlMaxC 100 [m
3
/h]]
Supply air VAV minimum air volume flow for cooling VavSuAirFlMinC 50 [m
3
/h]
Supply air VAV maximum air volume flow for heating VavSuAirFlMaxH 100 [m
3
/h]
Supply air VAV minimum air volume flow for heating VavSuAirFlMinH 50 [m
3
/h]
Supply air VAV maximum air flow for ventilation VavSuAflMaxVnt 100 [m
3
/h]
Supply air VAV minimum air flow for ventilation VavSuAflMinVnt 0 [m
3
/h]