Assortment / System Description

Fan
-
Powered Box
Application examples
19
A6V10866237_en--_b_08 151 | 275
An application with serial fan must transfer the fan state to the VAV controller
so that the VAV supplies only fresh air if the fan is also operating. This ensures
that no fresh air enters the room via the return air duct. The following image is
a diagram of the various locking and monitoring signals of a serial fan powered
box applications.
P Primary volume flow AirFlSu Supply air flow sensor
R Return air volume flow AirFlMx Mixed air flow sensor
F Fan volume flow TSu Supply air temperature sensor
AirFlSt Air flow state AirFlVavRe
q
VAV request signal to fan
FanSt Fan state AirFlHReq Request signal from heating
register to fan
AirFlHldH Switch-off delay signal from
heating register to fan
Figure: Serial FPB application