19.20 Presence control
The HVAC application can also be controlled by presence through the use of a
presence detector.
The HVAC application can be configured for each room to react to presence for
each room and regardless of the room operating mode.
Description Name Default value
Presence operating mode for Comfort
1:None
2:Considered presence
3:Considered absence
4:Considered presence & absence
PscModCmf 4:Considered
presence &
absence
Presence operating mode Pre-Comfort PscModPcf 4:Considered
presence &
absence
Presence operating mode for Economy PscModEco 1:None
Present operating mode for Protection PscModPrt 1:None
The applicable delays for the HVAC application in a room can also be
configured for each room.
Description Name Default value
Switching delay for presence SwiDlyPrst 5 Min
Switching delay for absence SwiDlyAbst 5 Min
19.21 Application examples
These are the descriptions of HIT applications on http://hit.sbt.siemens.com.
Visit the Siemens Download Center www.siemens.com/bt/download for the
latest application configurations.
19.21.1 Fan powered box
FPB051
Fan powered box with series fan
on analog output and staged
electric reheater on analog
output