Assortment / System Description

Heat pump application
Presence control
20
A6V10866237_en--_b_08 187 | 275
20.30 Presence control
The HVAC application can also be controlled by presence through the use of a
presence detector.
The HVAC application can be configured for each room to react to presence for
each room and regardless of the room operating mode.
Description Name Default value
Presence operating mode for Comfort
1:None
2:Considered presence
3:Considered absence
4:Considered presence & absence
PscModCmf 4:Considered
presence &
absence
Presence operating mode Pre-Comfort PscModPcf 4:Considered
presence &
absence
Presence operating mode for Economy PscModEco 1:None
Present operating mode for Protection PscModPrt 1:None
The applicable delays for the HVAC application in a room can also be
configured for each room.
Description Name Default value
Switching delay for presence SwiDlyPrst 5 Min
Switching delay for absence SwiDlyAbst 5 Min
20.31 Application examples
These are the descriptions of HIT applications on http://hit.sbt.siemens.com.
Visit the Siemens Download Center www.siemens.com/bt/download for the
latest application configurations.
20.31.1 Heat pump
HP001
Heat pump
with variable fan, reversing valve,
2-stage electric heating, 1-stage
electric radiator and outside air
damper
A6V10662238 en de