22.2 Stairwell lighting
The application provides scheduled switch off of lighting. Lighting is switched
on manually. After the overshoot time, it is automatically switched off. This
function is often used in stairwells and hallways. It is optimized for short
response times between pushing the button and the response by the lighting
actuator.
The room occupancy has the following commands available to manually
operate lighting:
Switch on
Switch off
Dimming up
Dimming down
All light applications have an automatic switch-off function A parameter is used
to enable the function. A second parameters determines the switch-off time.
A manually switched light application is configured to create stairwell lighting
with the function switched on for automatic switch off.
Description Name Default value
Automatic switch-off function
0:Disable
1:Enable
AutoOffFnct 0:Disable
Automatic switch-off time TiAutoOff 60 [s]
Automatic switch off