Assortment / System Description

Central applications
Automation station for HVAC supply and demand signals and manual control for lighting and blinds
24
250 | 275 A6V10866237_en--_b_08
Can configure whether the relief function can be activated in each room with
supply VAV for each VAV:
Description Name Default value
Enable relief
0:No
1:Yes
EnRlf 0:No
Air volume flow relief AirFlRlf 50 [m
3
/h]
Central functions can centrally override all VAV in a supply group. The following
parameters can be used.
Description Name Default value
Enable supply air VAV overridden value
0:No
1:Yes
EnVavSuOvrr 0:No
Supply air VAV overridden value VavSuOvrr 50 [m
3
/h]
Enable extract air VAV overridden value
0:No
1:Yes
EnVavExOvrr 0:No
Extract air VAV overridden value VavExOvrr 50 [m
3
/h]
Central override of VAV