Assortment / System Description

Central applications
Automation station for emergency controls for HVAC, light, and blinds
24
A6V10866237_en--_b_08 255 | 275
Description Name Default value
Central emergency shading products delay 1
0...7200 [s]
CenEmgShdDly1 10 [s]
Central emergency shading products delay 2
0...7200 [s]
CenEmgShdDly2 20 [s]
Central emergency shading products delay 3
0...7200 [s]
CenEmgShdDly3 30 [s]
All luminaires can be controlled during an emergency via a digital command.
The command is executed at the highest priority and cannot be locally
overridden in the room or from another central operation.
Lighting can only be manually or automatically operated after this digital
command is reset.
The emergency lighting control can be configured.
Description Name Default value
Emergency lighting level
1:Off
2:12.5%
3:25%
4:37.5%
5:50%
6:62.5%
7:75%
8:On
9:Undefined
EmgLgtLvl 8:On
The application repeats the command cyclically at the highest priority as long
as the digital command for lighting emergency control is active. The cycle can
be configured.
Description Name Default value
Cycle
0...60 [min]
Cycle 15 [min]
During an emergency, air HVAC devices in the room can be controlled via a
digital command. The command is executed at the highest priority and cannot
be locally overridden in the room or from another central operation.
HVAC plants can only be manually or automatically operated after this digital
command is reset.
All HVAC devices in the rooms are switched off if the digital command for HVAC
emergency shutdown is activated.
The function offers a test parameters that supports tests emergency reactions
regardless of digital input conditions on the fixed wired interface.
Description Name Default value
HVAC emergency test
1:None
2:Air volume flow off
3:Smoke extraction positive pressure
4:Smoke extraction negative pressure
5:Purge
TstHvacEmg 1:None
Light emergency control
HVAC emergency
shutdown