Assortment / System Description

Central applications
Automation station for weather station
24
A6V10866237_en--_b_08 259 | 275
The seasonal compensation application adjusts the room temperature
setpoints for Comfort heating and Comfort cooling based on outside
temperature.
Sp Setpoint for comfort TOa Outside temperature
SpHiCCmf Setpoint cooling high for comfort TOaLoC Outside air temperature low for
cooling
SpLoCCmf Setpoint cooling low for comfort TOaHiC Outside air temperature high for
cooling
SpHiHCmf Setpoint heating high for comfort TOaLoH Outside air temperature low for
heating
SpLoHCmf Setpoint heating low for comfort TOaHiH Outside air temperature high for
heating
Figure: Seasonal compensation
Description Name Default value
Setpoint cooling high for comfort SpHiCCmf 26 [°C]
Setpoint cooling low for comfort SpLoCCmf 24 [°C]
Outside air temperature high for cooling TOaHiC 32 [°C]
Outside air temperature low for cooling TOaLoC 26 [°C]
Setpoint heating high for comfort SpHiHCmf 23 [°C]
Setpoint heating low for comfort SpLoHCmf 22 [°C]
Outside air temperature high for heating TOaHiH 31 [°C]
Outside air temperature low for heating TOaLoH 25 [°C]
Seasonal compensation