Assortment / System Description

Central applications
Automation station for weather station
24
260 | 275 A6V10866237_en--_b_08
The application function reads the values from the wind sensor and smoothes
the value using switch on and off delays. The resulting value is then compared
to the configured limit values. In the event a limit value is breached, the blinds
products are deployed to a configured position. A position can also be
configured for a sensor fault as well.
The permissible limit value for switch on and switch off point must be
configured as per the design value of the installed shading products.
Description Name Default value
Switch-on point SwiOnPt 7 [m/s]
Switch-off point SwiOffPt 5 [m/s]
Switch-on delay protection function
0...300 [min]
DlyOnPrt 0 [min]
Switch-off delay protection function
0...300 [min]
DlyOffPrt 20 [min]
Command on limit exceed
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdLmExc 2:Open
Command on sensor fault
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdSenFlt 2:Open
Wind protection for all
facade products
CAUTION!