Assortment / System Description

Central applications
Automation station for weather station
24
A6V10866237_en--_b_08 261 | 275
The function is used to protect blinds or other facade products from mechanical
damage caused by icing. The application function reads the values of the
outside temperature sensor and precipitation detector. Frost protection is
activated if the outside temperature drops below a set limit and precipitation is
reported.
In the event of a frost warning, the blinds products are deployed to a configured
position. A position can also be configured for a sensor fault as well.
Frost protection is automatically reset if no precipitation is reported during a
configured period or the outside air temperature is above the limit value during
a configurable period.
Description Name Default value
Switch-on point
Limit value to trigger frost protection, only when
precipitation is present.
SwiOnPt 3 [°C]
Switch-off point 1
Reset temperature 1, only if there is no
precipitation.
SwiOffPt1 7 [°C]
Switch-off point 2
Reset temperature 2, only if there is precipitation.
SwiOffPt2 10 [°C]
Switch-on delay protection function DlyOnPrt 100 [s]
Switch-off delay protection function Frost
protection delay, if no precipitation exists and the
reset temperature 1 is exceeded.
DlyOffPrt 10 [h]
Switch-off delay reset Switch-off delay for frost
protection if reset temperature 2 is exceeded.
DlyOffRst 10 [h]
Command on limit exceed
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdLmExc 2:Open
Command on sensor fault (Frost protection monitor)
Note: Sensor fault precipitation must be configured
at CenPcpPrt11.
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdSenFlt 1:None
Frost protection for
blinds