Assortment / System Description

Central applications
Automation station for weather station
24
262 | 275 A6V10866237_en--_b_08
Use the function to protect awnings and other facade products against
moisture. The application function reads the values from the precipitation
detector and smoothes the value using switch on and off delays. The
precipitation warning resets automatically after the switch-off delay expires. In
the event of a precipitation warning, the awnings are deployed to a configured
position. A position can also be configured for a sensor fault as well.
Description Name Default value
Switch-on delay protection function
0...18000 [s]
DlyOnPrt 100 [s]
Switch-off delay protection function
0...50 [h]
DlyOffPrt 3 [h]
Command on limit exceed
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdLmExc 1:None
Command on sensor fault
1:None
2:Open
3:Height 25%, angle undef
4:Height 50%, angle undef
5:Height 75%, angle undef
6:Height 100%, angle 0%
7:Height 100%, angle 25%
8:Height 100%, angle 50%
9:Closed
CmdSenFlt 1:None
The factory settings for DXR2 facade protection are designed for blinds
products with active frost protection (temperature & precipitation). As a result,
the factory setting for the precipitation function is switched off and switched on
for frost protection. The configuration must be changed as follows when using
awnings:
Frost protection function. Command on limit
exceed
CmdLmExc 1:None
Precipitation protection Command on limit
exceed
CmdLmExc 2:Open
Precipitation protection
function for awnings
CAUTION!