Assortment / System Description

Control function
Room controller and setpoints
11
A6V10866237_en--_b_08 37 | 275
The control sequences for temperature control in a fan coil application can be
adapted through the following parameters:
Description Name Default value
Outside damper cooling sequence DmpOaCSeq 1
Radiated ceiling cooling sequence RcgCSeq 2
Heating/cooling coils cooling sequence HCclCSeq 3
Cooling coil cooling sequence CclCSeq 4
Fan cooling sequence FanCSeq 5
Radiator heating sequence RadHSeq 1
Radiated ceiling heating sequence RcgHSeq 2
Heating/cooling coils heating sequence HCclHSeq 3
Heating coils heating sequence HclHSeq 4
Fan heating sequence FanHSeq 5
The control sequences for temperature control in a VAV application can be
adapted through the following parameters:
Description Name Default value
Radiated ceiling cooling sequence RcgCSeq 1
Heating/cooling coils cooling sequence HcclCSeq 2
Cooling coil cooling sequence CclCSeq 3
VAV cooling sequence VavCSeq 4
Radiator heating sequence RadHSeq 1
Radiated ceiling heating sequence RcgHSeq 2
Heating/cooling coils heating sequence HCclHSeq 3
Heating coils heating sequence HclHSeq 4
VAV heating sequence VavHSeq 5
The control sequences for temperature control in a fan-powered box
application can be adapted through the following parameters:
Description Name Default value
Radiated ceiling cooling sequence RcgCSeq 1
Heating/cooling coils cooling sequence HcclCSeq 2
Cooling coil cooling sequence CclCSeq 3
Fan cooling sequence FanCSeq 4
VAV cooling sequence VavCSeq 5
Radiator heating sequence RadHSeq 1
Radiated ceiling heating sequence RcgHSeq 2
Heating/cooling coils heating sequence HCclHSeq 3
Heating coils heating sequence HclHSeq 4
Fan heating sequence FanHSeq 5
VAV heating sequence VavHSeq 6
The control sequences for temperature control in a heat pump application can
be adapted through the following parameters:
Fan coil application
VAV application
Fan-Powered Box
Heat pump application