Assortment / System Description

Control function
Room controller and setpoints
11
38 | 275 A6V10866237_en--_b_08
Description Name Default value
Outside damper cooling sequence DmpOaCSeq 1
Radiated ceiling cooling sequence RcgCSeq 2
Heating/cooling coils cooling sequence HCclCSeq 3
Fan cooling sequence FanCSeq 4
Radiator heating sequence RadHSeq 1
Radiated ceiling heating sequence RcgHSeq 2
Heating/cooling coils heating sequence HCclHSeq 3
Heating coils heating sequence HclHSeq 4
Fan heating sequence FanHSeq 5
11.4.7 Activate aggregates based on plant operating mode
You can configure how a room is cooled or heated for the plant operating mode
on DXR2. The following options are available separately as setting values for
heating and cooling:
Heating with radiators (radiator, ceiling heating)
Heating with air handling only (heating coils, electric reheaters)
Heating with both
Cooling with radiators only (chilled ceiling/beams)
Cooling with air handling only (cooling coils)
Cooling with both
Description Name Default value
Heating Comfort
1:None
2:Radiator
3:Air handling
4:Radiator & air handling
CmfCnf 4:Radiator & air
handling
Heating Pre-Comfort PcfCnf 4:Radiator & air
handling
Heating Economy EcoCnf 4:Radiator & air
handling
Heating Protection PrtCnf 4:Radiator & air
handling
Heating warm up WarmUpCnf 4:Radiator & air
handling
Cooling Comfort CmfCnf 4:Radiator & air
handling
Cooling Pre-Comfort PcfCnf 4:Radiator & air
handling
Cooling Economy EcoCnf 4:Radiator & air
handling
Cooling Protection PrtCnf 4:Radiator & air
handling
Cooling cool down CoolDnCnf 4:Radiator & air
handling
Cooling free cooling FreeCCnf 4:Radiator & air
handling