Assortment / System Description

Room coordination functions
Room functions: Room coordination
13
60 | 275 A6V10866237_en--_b_08
Reactions to the trigger can be configured for the specific discipline. The
following table provides an overview on a possible configuration.
Description Name Default value
Presence button
Eco Cmf
CmfCndTrg
3:Manual
HVAC: No impact
Lighting: On/start
constant lighting
control
Shading: Stop
automatic
function
Presence button
Cmf Eco
EefCndTrg
3:Manual
HVAC: Reset
setpoint offset
Lighting:
Immediate
off/stops
constant lighting
control
Shading: Enable
or manual
operation and
transition to
automatic
position.
Central scheduler
Cmf Eco
EefCndTrg
2:Automatic
HVAC: Reset
setpoint offset
Lighting: Off with
prior
flashing/stops
constant lighting
control
Shading: Enable
or manual
operation and
transition to
automatic
position.
Example