Assortment / System Description

Room coordination functions
Room functions: Room coordination
13
A6V10866237_en--_b_08 61 | 275
A manually adjusted setpoint for HVAC applications can be reset using the
trigger for "Energy efficiency condition". Control is reset to automatic. The
trigger acts on both the temperature setpoint as well as the setpoint for the fan
stage.
The application can also recognize whether the change to the room operating
mode from an automatic function or was the result of a manual operation. It
can be considered during configuration.
Description Name Default value
Fan command for the energy efficiency condition
trigger on automatic
1:None. The manual fan stage is maintained.
2:Automatic. The manual fan stage is reset.
FanCmdEefAuto 2:Automatic
Fan command for the energy efficiency condition
trigger on manual
FanCmdEefMan 2:Automatic
Operating command for the energy efficiency
condition trigger on automatic
1:None. The manual temperature setpoint is
maintained.
2:Automatic. The manual temperature setpoint is
reset.
OpCmdEefAuto 2:Automatic
Operating command for the energy efficiency
condition trigger on manual
OpCmdEefMan 1:None
For HVAC applications, rapid ventilation can be activated using the "Energy
efficiency condition" and "Comfort condition" trigger. This supplies a room with
rapid ventilation with fresh air for a configurable period.
The application can also recognize whether the change to the room operating
mode from an automatic function or was the result of a manual operation. It
can be considered during configuration.
Description Name Default value
Runtime rapid ventilation TiRnRpdVnt 60 min
Operating command for the energy efficiency
condition trigger on automatic
1:None. No reaction to trigger
2:Rapid ventilation. Rapid ventilation is enabled.
OpCmdEefAuto 1:None
Operating command for the energy efficiency
condition trigger on manual
OpCmdEefMan 1:None
Operating command for the Comfort condition trigger
on automatic
OpCmdCmfAuto 1:None
Operating command for the Comfort efficiency
condition trigger on manual
OpCmdCmfMan 1:None
Impact of the trigger on
HVAC