Assortment / System Description

Ceiling heating/chilled ceiling application
4-pipe heated/chilled beam with 6-port valve (PL-Link)
16
86 | 275 A6V10866237_en--_b_08
Description Name Default value
Chilled beam valve position X1
C
X1CcgVlvPos 0 [%]
Chilled beam valve position Y1
C
Y1CcgVlvPos 50 [%]
Chilled beam valve position X2
C
X2CcgVlvPos 100 [%]
Chilled beam valve position Y2
C
Y2CcgVlvPos 0 [%]
Heated beam valve position X1
H
X1HcgVlvPos 0 [%]
Heated beam valve position Y1
H
Y1HcgVlvPos 50 [%]
Heated beam valve position X2
H
X2HcgVlvPos 100 [%]
Heated beam valve position Y2
H
Y2HcgVlvPos 100 [%]
16.5 4-pipe heated/chilled beam with 6-port valve
(PL-Link)
Figure: Example for a 4-pipe heated/chilled beam application with a 6-port
valve (PL-Link)
Key:
DXR2… Automation Station R1 Room operator unit
YHC 6-port heated/chilled beam valve D1 Presence
CdnMon Condensation monitor D2 Window contact
Parameter settings
Plant diagram