Data Sheet for Application

Application Sheet
VAV041/VAV041_H
Supply and extract VAV with analog damper actuator, heating and
cooling coil on triac output
DXR2..12P-102A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662236_en--_d_--_01
Supply & extract air volume control with analog damper actuator
Room temperature control
Air quality control
Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature, air quality & relative humidity measurement
Plant diagram
Room automation station
R
Room
Extract air temperature sensor
R1
Room operator unit with
Supply air temperature sensor
temperature sensor
Differential pressure sensor (supply air)
YC
Cooling coil valve
Differential pressure sensor (extract air)
YE
Extract air control
Window contact
YH
Heating coil valve
Presence detector
YS
Supply air control
Function diagrams
Heating and cooling valve
Air flow
Effective cooling setpoint
VavSuAirFlMaxH
Max. volume, heating
Effective heating setpoint
VavSuAirFlMinC
Min. volume, cooling
Room temperature
VavSuAirFlMinH
Min. volume, heating
Volume flow rate
Y
Output signal
Min. air flow ventilation
YC
Cooling valve
Max. volume, cooling
YH
Heating valve
SpC
0
100
V [%] Y [%]
TR [°C]
YH
SpH
YC
VavSuAirFlMaxC
VavSuAirFlMinC
VavSuAirFlMinH
VavSuAirFlMaxH
SpC
0
100
V [%]
TR [°C]SpH
VavSuAirFlMaxC
VavSuAirFlMinC
VavSuAirFlMinH
VavSuAirFlMaxH
VavSuAflMinVnt

Summary of content (8 pages)