Data Sheet for Application

Application Sheet
VAV041/VAV041_H
Supply and extract VAV with analog damper actuator, heating and
cooling coil on triac output
DXR2..12P-102A
2 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662236_en--_d_--_01
Description
of functions
Basic functions
Options
PID control for supply VAV, temperature and air
quality.
Supply air differential pressure control sensor
integrated in controller.
Internal air flow controller controls supply air damper
actuator 0…10 V.
The temperature and air quality (CO
2
) is measured in
the room operator unit.
The application allows customers to adjust the room
temperature setpoints and rapid ventilation via the
room operator unit.
Display of room air quality on room unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
Extract air differential pressure sensor 0…10 V.
Heating and cooling coils with 3-position valves
controlled by triac outputs.
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions
Variants
Rapid ventilation.
Air volume flow tracking for positive and negative room
air pressure.
Air supply functions to coordinate demand signals for
pressure optimized fan control.
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
VAV application.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
Room operator unit and sensor variants:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP, 24 V,
DIN housing, 1 DI, 2 UI, 2 AO, 6 triac
N9205
N9207
DXR2.E12P-102A
DXR2.M12P-102A
1
R1
KNX PL-Link room operator unit with sensors for
temperature, humidity, CO
2
, segmented backlit
display, touchkeys
N1602
QMX3.P74
1
YS
Rotary air damper actuator, AC 24 V, DC 0…10 V,
5 Nm, 150 s
N4634
GDB161.1E
1