Alternate Room Pressure Monitor Solution Quick Start Guide A6V12012974 2020-04-23 Smart Infrastructure
Table of Contents Overview............................................................................................................................................... 4 Common Use Cases ..........................................................................................................................................5 Function ............................................................................................................................................................
Cybersecurity disclaimer Cybersecurity disclaimer Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.
Overview 0 Common Use Cases Overview Alternate Room Pressure Monitor Solution ● ● ● Visibly indicates correct or incorrect room pressurization for healthcare staff at the display panel. – Green LED = Isolation pressure acceptable – Red LED = Isolation pressure unacceptable Audibly alerts healthcare staff of incorrect room pressurization.
Overview Common Use Cases 0 Common Use Cases There are three typical use cases for the Alternate Room Pressure Monitor Solution: ● ● ● Basic operation Silent operation Synchronized operation Basic Operation – Alarm text and red light activate immediately when the door is opened and pressurization is lost. Audible alarm is silent unless the door stays open longer than a configured delay time. Silent Operation – Alarm text and red light activate only if the door stays open beyond a configured delay time.
0 Overview Function NOTICE Emergency Max Button – Do Not Use In the Alternate RPM Solution, the Emergency Max button on the ODP performs no function. If someone presses it by mistake, the red LED and buzzer respond for 1 second and then return to normal. Pressurization is not affected.
Configuration & Setup Function 0 Configuration & Setup Step 1 - In ABT Site, select Pressure monitor from Types in library. Step 2 - Select room pressure monitor(s) (CET room pressurization for room). Step 3 - For each room, make choice selections for: ● On-board input ● KNX PL-Link device ● HVAC When setting up multiple ODPs for multiple isolation rooms, the LED will flash and the display will show "Close the sash, Failed, Do not use" until all ODPs have been configured. This is expected.
0 Configuration & Setup Function Parameters Basic Operation Silent Operation Synchronized Operation Backlight brightness Set as desired Set as desired Set as desired Backlight timeout (1) Set as desired, max = 120min Set as desired, max = 120min Set as desired, max = 120min Rm DiffP alarm > Event parameters (2) TimeDelay: 0 TimeDelay: >0 Typically based on time needed to enter or exit the room TimeDelay: >0 Typically based on time needed to enter or exit the room Low limit: as specified L
Configuration & Setup Alarm Integration 0 Alarm Integration The Event Enrollment objects DiffPRAlm and AlmInd handle alarm integration for the Alternate RPM Solution. ● DiffPRAlm (Room differential pressure alarm) ● AlmInd (Alarm indication) The typical setup is audible with sound at the panel. This is the default configuration. To configure for non-default silent setup, do both of the following: ● Set DiffPRAlm parameter "Suppress event notification" to No.