Data Sheet for Product
Table Of Contents
Technical Specification Sheet
Document No. 149-1019
December 19, 2011
Siemens Industry, Inc.
Page 1 of 2
EcoView™ Multi-phase Meter
Description
The EcoView Multi-phase Meter is the multi-phase
power meter component of the EcoView System. It is
capable of measuring three-phase four-wire 240V wye
of up to 1200 Amps. The unit also has the ability to
interface to third-party water and gas meters via two
pulse inputs.
Factory calibrated, three-phase Current Transformers
(CTs) must be ordered separately.
Technical Specifications
Electrical Services Supported
• 120 Vac three-phase four-wire wye w/ neutral.
• 240 Vac single-phase three-wire.
Power and Reference Voltage
• For Single Phase and Three phase operation the
unit receives its operating power and reference
voltage from the ØA and N (Neutral) sense input.
Current Transformers
• 200A, 400A, 800A, and 1200A CTs supported.
• Max 25’ run from CTs to Multi-phase Meter.
• Split core for easy (no disconnect) installation.
ECO0016R1
1.84
(46.74)
6.59
(167.39)
6.10
(154.94)
4.34
(110.24)
TM
RSSI
MTR
PWR
NET PWR
G
N
ØA
ØB
MTR-1 MTR-2 A-CT B-CT C-CT 24VAC
ØC
Multi-phase Meter
Device-to-Panel Communications
• ZigBee 802.15.4 two-way link to Touchscreen.
• Range of 75 to 300 feet depending on local
conditions.
• Mesh networking with other EcoView products
allowing for greater range.
• Range boosting available via ZigBee Repeater.
Pulse Inputs
• Two optically isolated channels.
• 0 to 2000 PPS.
• 2.5 to 15V pulses.
• Either contact closure or electronic pulses.
• Can source power for remote devices.