Data Sheet for Product

Siemens
Building Technologies Division
Data Sheet 7360
usa.siemens.com/desigo-fire-safety
Product Overview
Used in co
rrelation to Siemens Desigo Fire Safety Modular system panels, the Single-
Node Upload (SNU) is an optional system module that provides a solution for
uploading
| downloading Desigo Fire Safety Modular system configuration data
remotely.
A given SNU can easily transmit information from a personal computer
run
ning the ZEUS-D custom-configuration tool to a maximum 64 Operator Interfaces
(
OIs | Model FCM2041-U2).
A dedicated Ethernet connection is the means used to allow SNU to directly
provide information from the
ZEUS-D tool to the remotely located Operator
I
nterfaces. Additionally, the Ethernet connection is separate from all existing
system networks (XNET
| HNET and DNET), as well as any other network devices.
A USB connector
used in regular ZEUS-D communication also provides the
physical connection bet
ween each Model FCM2041-U2 and the SNU module.
However,
for Desigo Modular (fire or fire/voice) systems that operate with the
legacy
central-processor interface, a serial cable (Model PMI-1 UPLD-CBL) must
be ordered f
or use with the SNU assembly.
See:
DETAILS FOR ORDERING
on the following
page.
Each SNU module ha
s three
(3) connections: Power |
Ethernet and USB. The data
transported between the
Z
EUS-D tool and the single-
node upload
is made through
a direct 128
-bit | Secure
Sockets Layer (SSL)
connection.
Desigo® Fire Safety
Modular system
Single-Node Upload (SNU) Module
Models SNU-KIT | SNU-ASSY | PS-5A
and PMI-1 UPLD-CBL
Architect & Engineer Specifications
Cost-
effective, highly efficient
processor designed for transmitting
bidirectional data between the ZEUS-D
tool and Desigo Fire Safety Modular
system panels connected remotely
Allows transferring and
extracting of information stored
in the Operator Interface (OI)
Up to 64 Desigo Fire Safety Modular
system panels can pass along system
data from as many SNU assemblies
Utilizes a dedicated (128-bit secure)
Ethernet cable connection
Universal Serial Bus (USB) cable is used
between Model FCM2041-U2 interface
modules and each SNU assembly
A serial cable (Model PMI-1 UPLD-CBL)
must be ordered for cable connection
between a legacy Person Machine
Interface module and each SNU
processor
One (1) Universal Serial Bus
(USB) cable is included in each
shipment of the SNU assembly
SNU hardware mounts in a separate
enclosure, Model ENCL-01
Each SNU assembly gets continuous
power from an integrated power supply
UL 864 10
th
Edition and UL 1076
Listed; ULC-S527 3rd Edition Listed,
CSFM (#7165-0067:02222) and
NYCFD (#6160A) Approved
Model SNU
Single Node
Upload Module

Summary of content (2 pages)