Operating instructions

Digital electronic modules
12.5 Parameters of the digital electronic modules
ET 200iSP
Operating Instructions, 01/2010, A5E00247483-04
261
8 DI NAMUR parameters, "8 DI NAMUR" configuration
Table 12- 17 Parameters for "8 DI NAMUR"
Parameters Range of values Default Applicability
Time stamping
1
enabled
disabled
disabled Channel
Edge evaluation event
entering state
1
rising edge (0-->1)
falling edge (1-->0)
rising edge (0-->1) Channel
Encoder type
Channel disabled
NAMUR sensor
Single contact, no load
resistance
Single contact, connected
with 10 kΩ
NAMUR changeover
contact
Changeover contact,
unconnected
Changeover contact,
connected with 10 kΩ
NAMUR sensor Channel
Pulse stretching
None
0.5 s
1 s
2 s
None Channel
Group diagnostics
enabled
disabled
enabled Channel
Diagnostics: wire break
enabled
disabled
enabled Channel
Diagnostics: wire break
enabled
disabled
enabled Channel
Diagnostics for chatter error
enabled
disabled
disabled Channel
External error
(changeover contact error or
faulty encoder supply)
enabled
disabled
disabled Channel
Chatter monitoring:
Monitoring window
2
0.5 s
1 s to 100 s (can be set in
1 s increments)
2 s Channel
Chatter monitoring: Number
of signal changeovers
2
2 to 31 5 Channel
1
Can only be assigned in HW Config and if the ET 200iSP is being operated as an S7 DP slave.
2
Parameter cannot be set unless chatter error diagnostics is enabled.