88 Operating Instructions, 01/2010, A5E00247483-04
Ambient temperature
Mounting positions
Power supply PS 24 VDC:
from -20 to 70°C
Power supply PS 120/230 VAC:
At 120 VAC
From -20 to 70°C (3A)
From -20 to 60°C (4A)
From -20 to 50°C (5A)
Power supply PS 120/230 VAC:
At 230 VAC
From -20 to 70°C (4A)
From -20 to 60°C (5A)
For horizontal installation of the ET 200iSP on a vertical wall
Power supply PS 24 VDC:
From -20 to 40°C (up to product
version 2 of power supply PS)
From -20 to 50°C (product version 3
and higher of power supply PS)
Power supply PS 120/230 VAC
from -20 to 50°C