Technical data

36 SIMATIC ET 200pro
Interface modules for PROFIBUS
The interface modules (IMs) for PROFIBUS can be combined
with three different modules for connecting the bus and pow-
er supply.
All connection modules for PROFIBUS have visible address
setters that allow the addresses to be easily read as well as a
selectable terminating resistor. The integrated T functionality
supports the start-up of partial segments and uninterrupted
bus communication in the event of a servicing requirement.
Direct connection with cable gland: For up to 16 A elec-
tronic load and a conductor cross-section of up to 2.5 mm².
ECOFAST (Energy and Communication Field Installation
System) – The standardized Siemens connection technique
for cabinet-free distribution is based on hybrid cables for
bus signals and power supply.
M12, 7/8'': The familiar connection method with widely im-
plemented connector standard.
Interface
modules
IM 154-1 DP
IM 154-2 DP HF
Protocol PROFIBUS DP
Transmission rate, max. 12 MBit/s
Firmware Update via PROFIBUS
Dimensions
(with connection module)
90 x 130 x 173 mm
with CM IP DP M12, 7/8"
90 x 130 x 120 mm
with CM IP DP directly
90 x 130 x 80 mm
with CM IP DP ECOFAST
Order No. group 6ES7 154-1.
6ES7 154-2.
PROFIBUS interface module,
ECOFAST connection
PROFIBUS interface module, M12,
7/8" connection
PROFIBUS interface module,
with direct connection