Object name Obj. type/ID Description BACnet Properties Modbus
BckpModValVfl
%Plt%HVAC'VlvCtl' BckpModValVfl
AV35 Backup mode value for volume flow
The volume flow in relation to the maximum volume flow
the device will go to, if:
Application is Dynamic control valve;
Control mode is Volume flow control;
Backup mode is Predefined setpoint.
Available in cloud N Address 173
Write Y R/W R/W
Unit [%] Resolution 0.01 %
Options Value min. 0 Min. 0
Value max. 100 Max. 10‘000
Default 0 Register 174
BckpModValPwr
%Plt%HVAC'VlvCtl' BckpModValPwr
AV36 Backup mode value for power
The power in relation to the maximum power the device
will go to, if:
Application is Dynamic control valve;
Control mode is Power control;
Backup mode is Predefined setpoint.
Available in cloud N Address 174
Write Y R/W R/W
Unit [%] Resolution 0.01 %
Options Value min. 0 Min. 0
Value max. 100 Max. 10‘000
Default 0 Register 175
BckpModValTFl
%Plt%HVAC'VlvCtl' BckpModValTFl
AV91 Backup mode value for flow temperature
The temperature setpoint the device will control, if:
Application is Supply temperature control;
Backup mode is Predefined setpoint.
Available in cloud N Address 175
Write - R/W R/W
Unit [°C] Resolution 0.01 °C
Options Value min. 0 Min. 0
Value max. 120 Max. 12‘000
Default 0 Register 176