Commissioning Instructions

55
Siemens A6V11422293_en--_d
Smart Infrastructure 2021-11-12
Commissioning: Heating circuit outside temperature-dependent
For relevant settings for heating circuit, see Operation: Heating circuit (outside temperature-
dependent) [ 75].
Valve mounting position and present values
1 2 3 4
Select Commissioning [1]. Select Valve [2]. Select Valve mounting mode [3] – this is the
only relevant setting.
Here, set whether the flow sensor is mounted
in the flow or return.
The other parameters are for information only
and do not influence the flow temperature
control loop.
Choose the mounting position of the flow
sensor [4]:
Return = flow sensor in the return from
the consumer
Flow = flow sensor on the flow from the
distribution network
E.g. as a 3-port valve in a mixing circuit