Commissioning Instructions

9
Siemens A6V11422293_en--_d
Smart Infrastructure 2021-11-12
13 14 15
Enter role [13.1]:
Administrator: Full access
Specialist: Balancing, control functions,
configuration
Installer: Balancing
Enter password [13.2].
Inital password for all roles: OneBT
First login requires a password change.
Password rules:
8 characters
1 number
1 special character
1 capital letter
Reset device to factory settings:
1. Press Service button [15.2] and WLAN button [15.4] at the same time for 10…15 s.
The LEDs [15.1; 15.3] slowly flash orange for 10 s.
The process can be cancelled during these 10 s by releasing the buttons.
2. After flashing for 10 s, the LEDs flash quickly for ca. 5 s; trigger the reset by releasing the
buttons.
3. The controller returns to normal operation without resetting if the buttons continue to be
pressed.
Remember your password!
Resetting the password resets
ALL settings.
All configurations, network settings, commissioning parameters, and
passwords are set will be set to factory settings.
This action cannot be cancelled or reversed.