User Manual

2
Siemens Building Technologies
Fire & Security Products
System overview
Detector line AlgoRex DS110x
Detector line Synova 600
(non-current limited)
Detector line Synova 300
(current limited)
Call point line
Mixed line
(detector/call point with
differentiation)
Intrinsically safe detectors
EX-area
24V
Linear smoke detector
or flame detector
Series MS6/7/9
Non-fire alarm
(technical alarm)
FBF
SD
ÜE
FAT
SST
Monitored control lines for
- horns, sirens
- beacons
Fire controls
- internal relays
- monitored control line
Remote transmission
- internal contact
- monitored control line
FBF fire brigade operating panel
SD fire key safe
ÜE alarm transmitter
Fire brigade indication terminal
Interface to connect
3rd party extinguishing control
VdS peripheral devices (DE)
Detector line Synova 300
with line continuity
according to BS 5839 Pt1
max. 5
max. 1
max. 32
max. 32
DC1192
SB3
FC10
FCE1003-B
3k9
FCE1004-F Line termination to fulfil VdS 2489
Detector line termination with three different types, depending on type of control unit.
Line termination with line continuity with diode
bases according to British Standard
Line termination STANDARD
Type 1
Type 2
Type 3
EOL
Various types with different features
Types Zones Control lines Power supply Battery size 7-segment
display
VdS
peripheral
devices
EOL
FC1008-A/-H 8 2 (+4) 2.5 A 17 Ah (x) - Type 1
FC1008-B 8 2 (+4) 2.5 A 17 Ah (x) - Type 2
FC1008-C 8 2 (+4) 2.5 A 17 Ah (x) - Type 1
FC1008-D 7 2 (+4) 2.5 A 17 Ah * (x) - Type 1
FC1008-E 8 2 + 4 (EVAC) 2.5 A 17 Ah x - Type 1
FC1008-F 8 2 2.5 A 17 Ah x x Type 3
FC1012-A 12 2 (+4) 2.5 A 17 Ah (x) - Type 1
FC1012-B 12 2 (+4) 2.5 A 17 Ah (x) - Type 2
FC1012-C 12 2 (+4) 2.5 A 17 Ah (x) - Type 1
FC1012-F 12 2 2.5 A 17 Ah x x Type 3
* if remote transmission card is used, only 7.2 Ah possible (x) = optional
Legend
Zones Number of detector lines (zones) for current
limited or non-current limited detectors (select-
able per line)
Control lines Number of monitored control lines providing
max. 500mA in state alarm, figure in brackets
stands for optional number (FCA1003), state
active programmable (steady/pulsating)
Power supply Max. available current on 24 V-side
Battery size Max. battery capacity (2 x 12 V) that fits into
the cabinet, left figure stands for 30 h of emer-
gency power operation (* = for 12 h)
7-segment
display
indication module for alarm counter, alarm
delay count-down, clock, event memory, etc.
factory-mounted or available as add-on
(FCA1002)
VdS peripheral
devices
facility to connect the VdS peripheral devices
(FSB, FAT, SD, ÜE, SST)
EOL type of end-of-line units as shipped with the
control unit (detail see above)